campus · WA · last checked 17 September 2026

Vantage Data Centers — Quincy Campus

Lifecycle label: operating; effective date not established Status evidence: Washington State Department of Ecology approval order dated 29 August 2023 Evidence: Independently source-linked Reuse: Reference only

Facts at a glance

Record ID
vantage-quincy-campus-wa
Record type
campus
Evidence confidence
medium
DataCenterData’s confidence in this record’s sourced fields, not in the project
Developer
Not named in the cited records
Operator
Vantage Data Centers
Owner
Owner of record not established
Tenant
Not named in the cited records
Capacity
49.5 MW Permitted backup generation · campus scope
Ecology states a 49.5 MW facility total for installed emergency generators in Phases One and Two. The component figures printed in the order do not sum to that total. This is permitted backup generation, not critical IT capacity, utility service or measured load. Phase Three equipment is outside the stated total.
Location
2101 M Street NE, Quincy, WA
County: Grant County
Exact location — The exact street address, city and county are stated in Ecology Approval Order 23AQ-E056; exact does not mean a surveyed parcel or building footprint.
Physical scale
The order describes a three-phase campus: Buildings One and Two were in place and Building Three was planned. This is not a finding that three buildings were operating on the review date.

What the sources support

Ecology's order calls this an existing data center at 2101 M Street NE. It says Buildings One and Two were in place while Building Three remained a future phase. Operating therefore describes the campus, not every planned building.

Definitions: record units · roles · capacity boundaries · lifecycle stages.

What remains unknown

Sources

Sourced classifications

Only values a cited source states for this site are shown; every other dimension is unknown. These are not national shares or rankings.

  • Cooling: Evaporative campus scope · official source · moderate confidence
    “The Permittee will utilize indirect evaporative cooling units to dissipate heat from electronic equipment at the facility, thus eliminating evaporative cooling tower emissions from the project.” — Approval Order No. 23AQ-E056 — Vantage-Quincy Data Center, PDF p.5, Equipment section, paragraph after the engine table (resolves to ecology.wa.gov/getattachment/3496318c-…/20230829VantageNOCpermit.pdf), retrieved 24 September 2026
    Not established: That the phases built after 2023 were built as described; that no supplemental mechanical cooling exists; water use; current operating condition of any unit.
  • Power source: On-site generation (backup, diesel or renewable diesel) campus scope · official source · high confidence
    “The list of equipment that was evaluated for this order of approval consists of five existing MTU Model 20V4000 diesel engines used to power emergency electrical generators” — Approval Order No. 23AQ-E056 — Vantage-Quincy Data Center, PDF p.3, Equipment section, retrieved 24 September 2026
    Not established: That the site operates on generator power; run-hours; that phases two and three were installed; normal power supply.

Connected records

Each connection below is a stored, reviewed relationship with its own basis. It does not change this record’s status.

Policy records

Record history

Record history · 29 August 2023 · DataCenterData review

vantage-quincy-campus-wa → Record

Why Ecology documented an existing two-phase campus and approved equipment for a third phase; the order is not evidence that the third building was complete or operating.

Evidence No additional evidence link; see the linked record or claim.

DataCenterData record added · 18 September 2026 · DataCenterData review

vantage-quincy-campus-wa → Publication

Why Added after independent re-reading of the state index and site-specific order, with backup generation kept separate from IT capacity.

Evidence No additional evidence link; see the linked record or claim.

Recorded information

What this page records, grouped by topic, with the source's units and qualifications. Company-reported values stay labeled as company-reported. Related listings are shown separately.

Reviewed record vantage-quincy-campus-wa

Campus · Vantage Data Centers. Independently reviewed record. Values are shown with their recorded basis.

Location and precision

  • Shown above in Facts at a glance.

Roles

  • Shown above in Facts at a glance.

Lifecycle

  • Recorded status: operating

Area, acreage and buildings

  • Shown above in Facts at a glance.

Power capacity

  • Shown above in Facts at a glance.

Not yet recorded here: Cooling, water, PUE and WUE · Connectivity · Services · Certifications and design ratings · Rack density · Availability · Specification links and contact · Permits, incentives, jobs and proceedings.

Update this profile with a public source. The request includes topics needing more information; this does not mean the facility lacks them. Corrections and additions are reviewed before publication.

Data + actions

Permanent link for citing this record →

Suggest a correction → Record ID vantage-quincy-campus-wa and the page are prefilled. Accepted material corrections appear on Changes.

Facility evidence across sources

Identity

Facility ID
dcd-fac-002583 (public id fac-002583)
Unit
campus
Name source
Vantage Data Centers — Quincy Campus · DataCenterData reviewed record vantage-quincy-campus-wa
Evidence tier
reviewed

Other names

Operators and presences

1 statement(s) naming an operator or presence at this site unit, one row per source. A building with several tenants is one facility with several presence rows.

Operator of record (reviewed): Vantage Data Centers.

Operator as statedRoleUnitStated byDate
Vantage Data Centers
Family: Vantage Data Centers
owner or operator (reviewed)campusDataCenterData reviewed record vantage-quincy-campus-wa

Status by layer

LayerValueDateSource
Reviewed (DCD) · verified recordoperating
Status basis: Ecology's order calls this an existing data center at 2101 M Street NE. It says Buildings One and Two were in place while Building Three remained a future phase. Operating therefore describes the campus, not every planned building.
Latest source retrieval/capture date DataCenterData reviewed record vantage-quincy-campus-wa

Capacity by kind

Each row is one kind of figure from one source. Utility, generation, design, critical IT and floor-area figures measure different things; they are never summed or totalled.

KindValue and evidenceScope and timingDateSource
Generation (MW)49.5 MW
Reviewed (DCD)

reviewed record

campusLatest source retrieval/capture date date not statedDataCenterData reviewed record vantage-quincy-campus-wa

Power and cooling on record

Records are grouped by system and may describe requests or plans. A highlighted group does not prove every named component is installed or operating. Labels name the source, not a confidence rating. A part with no record here may still exist. Each part links to how it works.

  1. 1 Grid connection and substation No record found yet
  2. 2 Transformers and switchgear No record found yet
  3. 3 Backup generators No record found yet
  4. 4 Data halls and servers No record found yet
  5. 5 Cooling inside the building No record found yet
  6. 6 Heat out Reviewed record

    Based on: Cooling type (reviewed) · See the evidence

  7. 7 Water in and out No record found yet

Location

Street
2101 M Street NE
City
Quincy
County
Grant
State
WA
Metro (CBSA)
CBSA 34180

Coordinates 47.248500269281, -119.815394999472 · precision street · DataCenterData reviewed record vantage-quincy-campus-wa

Address as published by DataCenterData reviewed record vantage-quincy-campus-wa.

Facts

Quote-bound facts: each shows the value, the source address, the capture hash (first 12 characters; the full SHA-256 is in the page markup) and the capture date. The source's exact wording stays in the capture record and is not republished here; the capture hash binds it.

No quote-bound fact with a hashed capture is recorded for this facility.

Other values by layer

FieldValueLayer and basisDateSource
physical scaleThe order describes a three-phase campus: Buildings One and Two were in place and Building Three was planned. This is not a finding that three buildings were operating on the review date.Reviewed (DCD) · reviewed recordLatest source retrieval/capture date date not statedDataCenterData reviewed record vantage-quincy-campus-wa
classification.coolingevaporativeReviewed (DCD) · reviewed classificationLatest source retrieval/capture date DataCenterData reviewed record vantage-quincy-campus-wa
classification.power sourceonsite_generationReviewed (DCD) · reviewed classificationLatest source retrieval/capture date DataCenterData reviewed record vantage-quincy-campus-wa

Sources for the reviewed record

These citations belong to the linked reviewed records. They do not establish every figure or present-day operating status. Publication and retrieval dates are shown separately; an unstated date remains unknown.

Details still needed

27 fields in the shared profile are not established for this record. Each states why; missing information does not mean zero or absence.

  • Postal code · not recorded for this field in the register
  • Provider-reported status · not recorded for this field in the register
  • Operator-stated status · not recorded for this field in the register
  • Status in public records · not recorded for this field in the register
  • Critical IT capacity (MW) · not recorded for this field in the register
  • Utility capacity (MW) · not recorded for this field in the register
  • Requested utility capacity (MW) · not recorded for this field in the register
  • Reported total power (MW) · not recorded for this field in the register
  • Company-announced design capacity (MW) · not recorded for this field in the register
  • Provider-reported capacity (MW) · not recorded for this field in the register
  • Floor area (sq ft) · not recorded for this field in the register
  • Data hall or IT floor area (sq ft) · not recorded for this field in the register
  • Site area · not recorded for this field in the register
  • Cooling redundancy · not recorded for this field in the register
  • UPS redundancy · not recorded for this field in the register
  • Backup generator redundancy · not recorded for this field in the register
  • Tier design rating · not recorded for this field in the register
  • Opening year or expected opening year · not recorded for this field in the register
  • Network presence · not recorded for this field in the register
  • Service · not recorded for this field in the register
  • Certification or compliance claims · not recorded for this field in the register
  • Rack density · not recorded for this field in the register
  • Space or power availability · not recorded for this field in the register
  • Specifications and facility pages · not recorded for this field in the register
  • Business contact · not recorded for this field in the register
  • Public registration · not recorded for this field in the register
  • Fact supported by a source quotation · not recorded for this field in the register

Jurisdiction and policy actions

Policy actions are matched to this facility by jurisdiction (state, county, municipality or utility), never by the facility's name. A match means the action covers the place, not that it names or affects this facility.

Updates, corrections and review

Last checked

How often we re-check

We plan to re-check this facility every 180 days because it has a reviewed record. Next check due . The last-checked date is the newest evidence date among this facility's sources. Dates are measured against the newest input date, , not the day this page was built.

Update this profile with a public source. The request includes topics needing more information; this does not mean the facility lacks them. Corrections and additions are reviewed before publication.

How complete the facility register is

Open identity review

These questions are open. Nothing has been merged or dismissed; a reviewer resolves each with captured evidence.

  • A possible duplicate of Vantage Quincy WA11 (fac-001586), Vantage WA13 (fac-001591) is under review (reason: city_only_ambiguous, opened ; hold hold-000090). Evidence needed: A street address, parcel id or coordinate source for the city-only row identifying which candidate (if any) it describes.
  • A possible duplicate of Vantage Quincy WA11 (fac-001586), Vantage WA13 (fac-001591) is under review (reason: address_shared_distinct_units, opened ; hold hold-000200). Evidence needed: A reviewer decision on whether the records sharing this address are suites or halls of one building, separate buildings, or a campus and its buildings (operator page, permit or parcel record naming the units).

Rights for this record

For each populated field, the origin of the value shown on this page and the terms it carries. Values that are not redistributable may be read and cited here but are not relicensed.

FieldSupplied byOriginLicenseAttributionRedistributable
current_nameDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
aliases[0]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
aliases[1]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
aliases[2]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
aliases[3]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
location.streetDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
location.cityDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
location.countyDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
location.street_keyDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
location.city_keyDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
location.stateDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
location.cbsaDataCenterData reviewed record vantage-quincy-campus-wadcd originalCC-BY-4.0DataCenterDatayes
location.latDataCenterData reviewed record vantage-quincy-campus-wapublic recordus government work public domainU.S. government source named on the recordyes
location.lonDataCenterData reviewed record vantage-quincy-campus-wapublic recordus government work public domainU.S. government source named on the recordyes
location.source_precisionDataCenterData reviewed record vantage-quincy-campus-wapublic recordus government work public domainU.S. government source named on the recordyes
presences[0]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
operator_of_recordDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
status_by_layer[0]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
lifecycle_statusDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
status_basisDataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
layer_values[0]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
layer_values[1]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
layer_values[2]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano
layer_values[3]DataCenterData reviewed record vantage-quincy-campus-wadcd reference onlyreference onlyDataCenterDatano